Furnace high limit switch codes by brand
A tripped high limit means the furnace got too hot. The codes below say so on nine different brands, and the cause is almost never the switch itself.
What the high limit switch does
The high limit is a temperature-sensing switch in the heat exchanger compartment that opens when the air leaving the furnace exceeds a set temperature. It is normally closed, wired in series with any other limits, and opening it shuts off the gas valve while leaving the blower running to clear the heat.
Why one part produces several different codes
A limit that opens is reporting a real overheat, and the overheat is nearly always a lack of airflow across the heat exchanger — a clogged filter, closed or blocked registers, an undersized or crushed return duct, a failed or slow blower motor, or a blower wheel packed with dirt. Replacing a limit switch that is doing its job correctly leaves the overheat in place and removes the protection against it.
Every high limit switch code on this site
15 codes across 9 control families. The meaning is the manufacturer's, from the document listed at the foot of each code page.
| Brand | Code | What it reports |
|---|---|---|
| Armstrong | 7 flashes | Primary or secondary limit open, or Watchguard after three minutes open |
| Goodman | 4 flashes | High limit switch is open — the furnace is overheating |
| Goodman | 6 flashes | Rollout limit open, or control module fuse blown |
| Goodman | E3 | High limit switch is open — the furnace is overheating |
| Goodman | 11 red flashes | Limit switch open due to blower failure |
| Goodman | 4 red flashes | Open limit switch |
| Heil | 4 flashes | Limit switch string is open |
| Heil | 7 flashes | Soft lockout — limit trips taking longer than two minutes to reset |
| Lennox | Alert code 200 | Rollout limit switch open |
| Lennox | Alert code 251 | Primary limit switch open |
| Lennox | Alert code 274 | Primary limit switch open more than three minutes — Watchguard |
| Rheem | 3 blinks | Limit switch open |
| Trane | 4 flashes | Open high limit device |
| York | 11 red flashes | Limit switch open more than five minutes — blower failure |
| York | 4 red flashes | Open high limit switch |
Before you work on it
Repeated limit trips overheat the heat exchanger, which is the component whose failure lets combustion gases into the supply air. A furnace that keeps tripping on limit needs the airflow problem found, not the limit replaced.
Other parts
- Furnace pressure switch codes on every brand
- Furnace flame sensor codes on every brand
- Furnace rollout switch codes: why it tripped
- Furnace igniter fault codes by manufacturer
- Furnace inducer motor fault codes by brand
- Furnace gas valve fault codes by manufacturer
- Furnace grounding and reversed polarity codes
Sources
Every code meaning above comes from the manufacturer document behind its code page:
- Allied Air Enterprises — A80UH1E and 80G1UHE Installation Instructions 507330-03, Table 7: Diagnostic Codes for -02 Control
- Goodman Manufacturing — Diagnostic Code Identification System (model-specific fault code lookup)
- International Comfort Products *9MPT and *9MPV installation instructions — Gas Valve Diagnostic Codes (third-party archive of the ICP document)
- Lennox Residential Communicating Systems Alert Code Guide, document 100017, March 2023 — Table 2, Alert Codes and Troubleshooting
- Rheem Professional Technical Support — Standard Gas Furnace Diagnostic Flash Codes
- Trane Installer's Guide 18-CD29D1-14-EN — Table 21, Integrated Furnace Control Error Flash Codes
- Johnson Controls Unitary Products technical service letter ST-045-09 — York UTEC furnace boards, fault code tables and retrieval procedure