Trane and American Standard furnace flash codes
Trane's integrated furnace control reports faults as a flash count, and uses the flash rate itself to signal normal operation — slow for idle, fast for a call for heat.
Also covers: American Standard — same manufacturer, same controls, same codes.
Trane and American Standard are the same manufacturer and use the same integrated furnace control. Unlike most manufacturers, Trane uses the rate of flashing as well as the count: a slow steady flash means idle with no call for heat, and a fast steady flash means the furnace is responding to a call. Neither is a fault. Counted flashes from two to nine are the actual fault codes.
Worth knowing before you count
Fast flashing means normal operation on a Trane control and means a fault on several other manufacturers' boards. If you have owned a different furnace before, that convention does not carry over. A steadily lit LED that never flashes is Trane's instruction to replace the control.
How Trane furnaces signal codes
Trane runs two diagnostic systems side by side, and they share no numbering at all. The flash-code system is a single LED counting out faults from two to nine, with the flash rate itself carrying the normal-operation states. The seven-segment system, used on two-stage variable speed furnaces such as the S9V2, shows alphanumeric codes like E2.1 and E3.2 on a small display with Menu and Option buttons beside it — and the display shows something at all times, including IdL for idle and Xt1 for first stage heat, so characters on the screen are not automatically a fault. The tell is simple: if you are counting blinks you are on the flash-code system, and if you are reading characters you are on the seven-segment system. The seven-segment control also stores the last six faults in a menu, which means an intermittent fault that cleared itself is still recoverable — worth knowing before anyone holds the Option button for five seconds, which erases that list.
The Trane codes people look up most
On the flash-code side: 4 flashes is an open high limit, which is an airflow question — a clogged filter more often than a bad switch; 3 flashes is a draft pressure error pointing at the inducer and venting; 2 flashes is the lockout that follows too many failed ignition attempts; 8 flashes is a low flame sense signal, classic dirty-flame-sensor territory; and 9 flashes is an igniter circuit problem. Each has a seven-segment sibling — E04, E3.2, E2.1, E08 and E6.3 respectively — that describes the same physical fault on the other control, which is useful when a code was reported second-hand as a bare number.
Which Trane furnaces these pages cover
The flash codes are documented from Trane Installer's Guide 18-CD29D1-14-EN, Table 21, which covers the integrated furnace control used on Trane's flash-code furnaces. The seven-segment codes come from Installer's Guide 18-CE01D1-1E-EN for the S9V2 two-stage condensing variable speed furnaces. American Standard is the same manufacturer using the same controls, so both tables apply to equivalent American Standard models. If a code will not resolve against one table, check which system the furnace actually has before assuming the code is wrong.
What the common Trane fixes cost
The 8-flash and E08 low flame signal usually ends at flame sensor cleaning, $80–200 — the classic ten-minute fix. The 9-flash and E6.3 igniter faults run $150–350 installed, with the part $20–60 universal. Pressure switch codes (3 flashes, E3.2, E3.4) are $150–400 with the flue checked first; an open limit (4 flashes, E04) is $150–350 plus finding the airflow problem that tripped it. A continuously lit LED or E01 points at the control itself — $400–900 installed, though E12's open fuse is the $5–150 repair that impersonates a dead board. Blower communication faults E17 and E18 land in ECM territory: $700–1,200, or $900–1,500+ for variable-speed.
Trane and American Standard
- 2 flashes — System lockout — retries or recycles exceeded
- 3 flashes — Draft pressure error
- 4 flashes — Open high limit device
- 5 flashes — Flame sensed when no flame should be present
- 6 flashes — 115 volt AC power reversed, or poor grounding
- 7 flashes — Gas valve circuit error
- 8 flashes — Low flame sense signal
- 9 flashes — Ignitor circuit problem, or low voltage between neutral and 24 volt common
- Continuous off — Check power
- Continuous on — Replace the integrated furnace control
- Flashing fast — Normal — call for heat
- Flashing slow — Normal — no call for heat
Trane and American Standard seven-segment codes
- E01 — Internal control failure
- E2.1 — Retry exceeded — flame never sensed, one hour lockout
- E2.2 — Recycles exceeded — flame sensed then lost, one hour lockout
- E2.3 — First stage gas valve not energised when it should be, ten times
- E3.2 — Open pressure switch, first stage
- E3.4 — Open pressure switch, second stage
- E3.1 — Shorted pressure switch, first stage
- E3.3 — Shorted pressure switch, second stage
- E04 — Open limit — thermal, rollout, or reverse airflow switch
- E05 — Flame detected when it should not be present
- E6.1 — Line voltage polarity reversed
- E6.2 — Bad grounding
- E6.3 — Igniter relay failed, or igniter open
- E7.1 — First stage gas valve energised when it should be off
- E08 — Flame current low but still usable
- E09 — Open inducer limit switch or condensate pressure switch
- E11 — Gas valve relay faults — five conditions in one code
- E12 — Open fuse
- E17 — Blower motor not responding to communication
- E18 — Blower communication failure on the control
- IdL, Xt1, Xt2, aRF and the other status codes — Normal operation — the display is not showing a fault
- Which Trane code system you have — Trane furnaces use either flash codes or a seven-segment display, and they share no numbering
Other manufacturers
- Goodman and Amana furnace fault codes
- Carrier, Bryant and Payne furnace status codes
- Lennox furnace alert codes
- York, Luxaire and Coleman furnace flash codes
- Rheem, Ruud and Weather King furnace blink codes
- Heil, Tempstar and Comfortmaker furnace codes
- Armstrong Air, AirEase, Concord and Ducane furnace codes