Lennox furnace E250: Limit switch circuit open

E250 means the limit switch circuit is open — the furnace is overheating. If the limit does not close within three minutes, the furnace goes into a one-hour soft lockout.

Applies to: Lennox gas furnaces with a seven-segment diagnostic display on the control board, such as the ML193UHEK, per installation instructions 508565-01. On Lennox's communicating alert code list, 250 means something completely different.

What it means

The limit circuit is a string of normally-closed temperature switches that open when the air leaving the furnace gets too hot. Opening the circuit cuts the gas while leaving the blower running to clear the heat. Lennox specifies the timing precisely: if the limit has not closed within three minutes, the unit drops into a one-hour soft lockout, which is why a furnace with this fault often appears to work for one cycle and then go quiet for an hour. The cause is almost never the limit switch. Lennox's own steps name the firing rate, blockage in the heater, and airflow — all of which are the furnace producing more heat than the air can carry away.

Most common causes

How to diagnose it

  1. Check the air filter first and replace it if dirty. Homeowner work, and often the whole repair.
  2. Walk the house and confirm registers and returns are open, including under furniture.
  3. Note whether the furnace runs for a few minutes and then stops with the blower still going — that is this fault's signature.
  4. Confirm the code came from the display on the control board, not the thermostat. Alert code 250 on a communicating system is flame sensed out of sequence, an unrelated and more urgent fault.

How to fix it

  1. Replace a dirty filter and clear blocked registers, then see whether it returns.
  2. If it returns with clean filters and open registers, the restriction is in the ductwork or the blower — technician work.
  3. Replacing a limit switch that is doing its job leaves the overheat in place and removes the protection against it.
  4. Repeated limit trips stress the heat exchanger, which is the part whose failure lets combustion gases into the supply air.

Notes

This is the specific code where Lennox's two systems disagree, and the disagreement matters: airflow problem on one list, gas valve concern on the other.

Related

All codes for this manufacturer

Lennox furnace alert codes — every code, with what differs between models.

This code is not a homeowner repair. Faults in this group involve the gas valve, the burner compartment, or the heat exchanger — the parts whose failure can put combustion products, including carbon monoxide, into the air the house breathes. Do not reset it repeatedly to keep the heat on. Have it looked at by a licensed technician, and make sure there is a working carbon monoxide alarm on every level of the home, including the level the furnace is on.

Sources

This site is a reference, not a substitute for a licensed HVAC technician. Gas appliances can leak carbon monoxide and cause fire. Anything involving gas lines, the heat exchanger, or the flame sensing circuit should be handled by a licensed professional. Pages are written with AI assistance from the sources listed on each page and checked against them before publishing.