Trane furnace E05: Flame detected when it should not be present
E05 means the control is reading a flame at a time when the gas valve should be closed and nothing should be burning. It points at a gas valve passing gas, or at a sensing circuit reporting a flame that is not there.
Applies to: Trane and American Standard S9V2 two-stage condensing variable speed gas furnaces with a seven-segment integrated furnace control display, per Installer's Guide 18-CE01D1-1E-EN.
What it means
The control checks the flame sensor during windows when no flame should exist. Detecting one in that window has two possible explanations and one of them is serious. Either the gas valve is leaking through when commanded shut, which puts gas into a hot chamber with no controlled ignition, or the sensing circuit is shorted and reporting a flame that is not present. This control has several related codes that narrow it down — E7.1 reports the first stage gas valve energised when it should be off, which is an electrical fault rather than a mechanical leak. But E05 on its own does not distinguish a leaking valve from a shorted sensor, and the safe assumption is the leak.
Most common causes
- A gas valve leaking through when it is commanded closed.
- A short in the flame sensing circuit reporting a flame that is not present.
- A burner still glowing hot enough after shutdown to produce a signal.
- Damaged or shorted flame sensor wiring.
- A failed control board misreading the sense input.
How to diagnose it
- Do not investigate this with the furnace running. Shut the gas off at the manual valve.
- If there is any smell of gas, leave the building and call the gas utility from outside.
- Check the Last 6 Faults menu for a stored E7.1, which would point at the valve being energised rather than leaking.
- Everything beyond shutting off the gas belongs to a licensed technician.
How to fix it
- Shut off the gas supply to the furnace.
- Call a licensed technician. This is not a homeowner repair under any circumstances.
- Expect the gas valve to be checked for leak-through and the sense circuit checked for a short.
- A furnace that has recorded this should not be left running while it is investigated.
Notes
The Trane flash code system reports the same condition as five flashes. The meanings agree between Trane's two systems here, which is not something to rely on generally.
Related
- 5 flashes — Flame sensed when no flame should be present
- E04 — Open limit — thermal, rollout, or reverse airflow switch
All codes for this manufacturer
Trane and American Standard furnace flash codes — every code, with what differs between models.