Furnace overheats and trips the high limit

The furnace lights normally, runs for several minutes, then shuts the burners down while the blower keeps going. It is overheating, and the cause is almost never the limit switch itself.

What is actually happening

The high limit is a normally-closed temperature switch in the heat exchanger compartment that opens when the air leaving the furnace exceeds a set temperature. Opening it cuts the gas valve while leaving the blower running to carry the heat away. A furnace that keeps tripping on limit is a furnace that is producing more heat than the airflow can remove.

What causes it

Nearly every cause is a lack of airflow: a clogged air filter, closed or blocked supply registers, blocked return grilles, an undersized or crushed return duct, a blower wheel packed with dirt, or a blower motor running slow or not at all. Several manufacturers publish a separate code specifically for a limit that opened because the blower failed, which is the same overheat with the cause already identified. Less common but real: an oversized furnace for the duct system, or a gas pressure set too high.

The codes that report this

11 codes across 9 control families. Each links to what that manufacturer says about it.

BrandCodeWhat it reports
Armstrong7 flashesPrimary or secondary limit open, or Watchguard after three minutes open
CarrierStatus code 13Limit circuit lockout
Goodman4 flashesHigh limit switch is open — the furnace is overheating
GoodmanE3High limit switch is open — the furnace is overheating
Goodman11 red flashesLimit switch open due to blower failure
Heil6 + 4 flashesSoft lockout — limit circuit opened during the run
Heil7 flashesSoft lockout — limit trips taking longer than two minutes to reset
LennoxAlert code 251Primary limit switch open
LennoxAlert code 274Primary limit switch open more than three minutes — Watchguard
Rheem3 blinksLimit switch open
York11 red flashesLimit switch open more than five minutes — blower failure

Worth knowing

Replacing a limit switch that is doing its job leaves the overheat in place and removes the protection against it. Repeated limit trips stress the heat exchanger, and the heat exchanger is the component whose failure puts combustion gases into the supply air. Find the airflow restriction.

Other symptoms

This site is a reference, not a substitute for a licensed HVAC technician. Gas appliances can leak carbon monoxide and cause fire. Anything involving gas lines, the heat exchanger, or the flame sensing circuit should be handled by a licensed professional. Pages are written with AI assistance from the sources listed on each page and checked against them before publishing.