Furnace Fault Codes

Goodman furnace 6 red flashes: Pressure switch cycle lockout

Six red flashes means the pressure switch has opened and closed too many times within a cycle, so the control has locked out rather than continuing to retry.

Applies to: Goodman GMEC96 and Amana AMEC96 two-stage gas furnaces with a three-colour diagnostic LED.

What it means

This is not a single pressure switch failure but a pattern of them. The switch is closing, proving draft, then opening again during the cycle — repeatedly. The control counts those events and, past a limit, stops rather than continuing. That behaviour points at something different from a switch that simply will not close: a marginal or intermittent draft, where the furnace can prove draft momentarily but cannot hold it. Wind at the termination, a partly restricted vent, or a condensate trap that fills during the cycle all produce this pattern, and all of them are conditions that come and go rather than being consistently present.

Most common causes

How to diagnose it

  1. Note that this is a repeated fault rather than a single one, which points at an intermittent condition.
  2. Check the outside vent termination for partial restriction, and note the weather — wind and freezing conditions both fit.
  3. Check the condensate drain for slow drainage rather than complete blockage.
  4. Note whether the fault happens more on long runs than short ones, which fits a condition that develops during a cycle.
  5. Listen to the inducer for any change in note during a run.

How to fix it

  1. Clear the vent termination and condensate drain if either is partly restricted. Both are within homeowner reach.
  2. The pressure switch, its hose, and the inducer are technician work.
  3. Have the vent system assessed properly if the restriction is not obvious. A marginal draft is harder to find than an absent one, and it produces exactly this code.
  4. Never bypass the pressure switch. An intermittent draft is still a draft problem.

Notes

Intermittent faults are the hardest to catch because the furnace often works when a technician visits. Recording when this happens — time of day, weather, how long the furnace had been running — is genuinely useful and is something only the householder can do.

Related

All codes for this manufacturer

Goodman and Amana furnace fault codes — every code, with what differs between models.

Not sure this is your brand?

The same count means something else on other furnaces. What 6 flashes means on every brand puts them side by side.

Models this code appears on

From the manufacturer's per-model database. If your model is not listed, this code may not exist on your board, or it may mean something different — check the model page.

The same fault on other control families

Cycle lockout is the pressure switch code for a draft that keeps faltering rather than failing outright — the switch closes, opens mid-cycle, closes again, until the control stops tolerating it. York's six red flashes defines it identically on the sibling table. The pressure switch code hub places it among the forty-seven pressure switch codes it tracks, where it stands out as the intermittent one: most of its relatives describe a switch that never moves, this one describes a switch that will not stay put.

What the fix costs

Budget in the pressure switch band — $150–400 per the repair cost guide, with the guide's check-the-flue-first caution applying doubly here, because an intermittent fault usually means marginal venting rather than a broken part: a partially obstructed termination, a sagging vent run holding condensate, or wind pressure at the termination can all cycle a healthy switch. If the draft is faltering because the inducer is, that is the $300–900 branch. The intermittency also means a technician may need conditions on their side, so a clear description of when it happens is worth real money on this one.

DIY or call a pro?

The homeowner contribution is the pattern: does the lockout follow windy weather, heavy snow, or hard rain? Does it happen at the start of cycles or partway through? Notes like these turn an intermittent fault — the kind that behaves perfectly during the service visit — into a solvable one. The outdoor terminations are yours to inspect and clear as with any venting code. Indoors is the technician's: tracing marginal draft means watching manometer readings through a full cycle on a live furnace. Do not keep resetting the lockout to coax heat out of it; the control counted those switch flutters for a reason.

What this looks like

From the outside, this usually shows up as the furnace starts and stops in short bursts — that walkthrough covers what to check in order, and when it stops being a homeowner job.

Sources

This site is a reference, not a substitute for a licensed HVAC technician. Gas appliances can leak carbon monoxide and cause fire. Anything involving gas lines, the heat exchanger, or the flame sensing circuit should be handled by a licensed professional. Pages are written with AI assistance from the sources listed on each page and checked against them before publishing.